Price is without discount and VAT
The INTU FR GRAPHITE is graphite fire-retardant mass swells under the influence of fire, closing the opening around the installation and any gaps, creating a barrier that ensures the partition remains tight and insulating up to EI 120.
Where to use:
The intumescent graphite sealant INTU FR GRAPHITE is intended for fire protection of penetration seals, specially:
- combustible pipes diameter of Ø ≤ 110mm
- bundles of copper pipes for air conditioning
- single cables and cable bundles
- cables in casting pipes and AROT type pipes
Flexible walls:
The wall must be minimum 100 mm thickness with a frame structure of steel or wooden sections covered on both sides with a minimum of 2 layers of panels with a thickness of min 12,5 mm.
Rigid walls:
The wall must be minimum 100 mm thickness, made of concrete, reinforced concrete, concrete blocks, cellular concrete, ceramic brick (solid, hollow or lattice) or silicate brick (solid or hollow) with a density of min. 450 kg/m3.
Rigid floors:
The floor must be at least 150 mm thick made of concrete, reinforced concrete or cellular concrete with a minimum density of 550 kg/m3.
Compliance:
- Test standard:
EN 1366-3 / EAD 350454-00-1104 - European Technical Assessment:
ETA 24/0152 of 28/03/2024 - Declaration of Performance:
DoP 3/2024 - Certificate of Constancy of Performance
1488-CPR-1109/W
Installation: